Magnetostrictive Displacement Sensor Fieldbuses: CANopen vs Profibus for Position Feedback

CANopen and Profibus both look like serial buses, but CANopen runs on a CAN differential pair, not the Profibus RS-485 layer. Serial fieldbuses already include two types: 194 CANopen and 195 Profibus DP. Roles: CANopen is controller and node; Profibus is master and slave. This page compares those two only.

Physical layer comparison of CANopen and Profibus for displacement sensors
CAN pair versus Profibus pair with their own termination

Separate the physical layers first

CANopen (194)Profibus DP (195)
Physical layerCAN differential pair — not RS-485RS-485 twisted pair
Application layerCANopen (position per DSP406)Profibus DP
Description fileEDSGSD
Termination120 Ω at both ends of the segmentEnd plugs ON, and that device must be powered
Cable lengthHigher baud, shorter allowed lengthThe same inverse rule

Terminate CAN with 120 ohm at both ends; on Profibus the end plug must sit on a powered device, not a parked one. Treating CAN as RS-485 when you buy plugs, terminators and repeaters shows up as error frames and intermittent faults. Termination and length: why it has to be 120 Ω.

CANopen (194) — advantages

  • Mobile controllers on excavators, implements and access platforms almost always have CAN, so joining the machine network is cheap.
  • Several rods share one shielded pair, unlike one analogue pair per axis.
  • Position on PDO, parameters on SDO; faults can be raised with EMCY without polling.
  • DSP406 already places the position objects, so a type swap need not rewrite the mapping.
  • Several magnets on one waveguide can map to several PDOs; analogue cannot.

CANopen — disadvantages

  • Bandwidth and cycle determinism are below EtherCAT / PROFINET; it is not a drop-in for industrial Ethernet.
  • SYNC is a medium synchronisation tool; strict simultaneous sampling belongs on the Ethernet pair.
  • Baud must be identical on the whole network; one wrong node can take the bus down.
  • Topology is a line with short drops, not a star. Missing end termination or extra resistors in the middle both reflect.

Object dictionary and baud: 194 explained, PDO/SDO.

Profibus DP (195) — advantages

  • Many S7-300 / S7-400 lines still run DP; replacing the rod need not replace the PLC or the trench.
  • GSD import, station numbers and diagnostic telegrams are familiar to electricians.
  • Polled diagnostics can tell “no response” from a parameter or configuration mismatch — better than a single analogue current.
  • The dedicated plug is a feed-through; unplugging a middle station usually leaves the trunk intact (end plugs excepted).

Profibus — disadvantages

  • New projects rarely choose it on purpose; a new Siemens CPU speaks PROFINET.
  • Master–slave polling has no DC / IRT sample-time alignment.
  • The terminating plug must sit on a powered end device; parking it on a dead station is the same as no match.
  • At high baud, spurs must stay short — same as CAN, you cannot star-wire by habit.

GSD and diagnostics: 195 explained, GSD configuration.

One-line choice

  • Mobile machine, CAN already on the controller: 194.
  • Installed Siemens DP network: 195.
  • New S7-1200/1500: do not keep Profibus just because it is still Siemens — see 199 PROFINET.
  • Fast multi-axis sync: neither serial bus is first choice; look at EtherCAT.

Four-bus table: comparing the whole fieldbus range. Output types: output signals compared.

Frequently Asked Questions

Q: Charts label CAN as RS-485 — can I share the cable plant?

Do not treat CAN as RS-485. Physical layers differ. 194 uses a CAN pair and 120 Ω at both ends; 195 is the Profibus RS-485 plug terminator.

Q: Should a new project still pick 195?

If the master is already S7-300/400 DP, 195 is the cheap path. If the new CPU is S7-1200/1500, choose PROFINET rather than keeping DP for familiarity.

Q: Do both buses need terminating resistors?

Yes. CAN: 120 Ω at both ends. Profibus: end plugs ON, and that device must be powered. The two Ethernet types do not need them.

Q: Can Modbus-RTU and Profibus share one port?

No. Both may use RS-485, but protocol, baud, termination and GSD/station numbers are different families. How Modbus reads position is a separate briefing; it is not the same port as 195.