Magnetostrictive Displacement Sensor Head LEDs: OK, No Magnet, Over-Range

On power-up, the head LEDs of a magnetostrictive displacement sensor tell you supply, magnet and range status before any meter is used. Read the electronics-head LEDs before unplugging. Analogue / SSI heads commonly have two lamps: green means the module is alive, red means the measuring condition is not met.

Electronics-head LED diagnostic table on a magnetostrictive displacement sensor
Head LEDs: green and red combinations and what each means

Lamp table

LampsMeaningNext
Green on, red offOK, magnet seenAlign reading and stroke; do not chase a missing supply
Green on, red onNo magnetFallen / reversed magnet, air gap, or left the valid stroke (over-range)
Both offNo supply, or module deadMeasure +24 V; see troubleshooting and multimeter 5 steps

Over-range and no-magnet often share the same lamps: the magnet entered a dead zone or left the rod. When both lamps are on, move the magnet to mid-stroke; if the lamps recover it was an over-range excursion, not a dead magnet. Lamps should return to green on / red off. If they stay dual-on at mid-stroke, it is the magnet or air gap.

With a multimeter

  1. Both off: measure 20.4–28.8 V, polarity and connector.
  2. Both on: move the magnet / piston before opening the head.
  3. Lamps OK but the reading jumps: routing, shield, ripple — n9.

SSI (162 / 192) uses the same lamps; protocol: 162 vs 192. Fieldbus link lamps: drop-outs.

Engineer's notes

  • Fieldbus heads carry two sets of lamps. 194 (CANopen), 195 (Profibus DP), 197 / 198 (EtherCAT) and 199 (PROFINET) add a link lamp to the measuring lamps. A dropped node or lost frames is a link-lamp question first — measuring lamps being fine does not mean data reached the PLC.
  • Lamps report measuring conditions, not accuracy. Green means there is an echo to read. Jitter and non-linearity do not show up on lamps; those go to routing, shielding and ripple.
  • SSI uses the same lamp codes as analogue. 162 / 192 follow the table above; do not go looking for different lamp positions because the protocol changed.

Frequently Asked Questions

Q: Both lamps on — is the sensor dead?

Usually not. It means no magnet: fallen, reversed, air gap, or over-range / dead zone. Go to mid-stroke first.

Q: Lamps OK but the PLC has no value?

Supply and magnet are satisfied. Check output type, pin count, shield and PLC channel setup.

Q: Does Series 18 four-pin voltage use the same two lamps?

Follow that head's markings. Swapping supply and signal burns the sensor — do not rely on lamps alone.

Q: What if red flashes?

The usual spec is steady combinations for OK / no magnet. If you see flashing, check that type's note and confirm 20.4–28.8 V.

← Back to News